Monitoring system SMT-EE is designed for transformer on-line diagnostics. It consists of Hydrocal device for gas-in-oil and moisturein-oil measurements, ZVCM 1001 device for bushings monitoringand SMT software for data visualization and processing. Additional signals from temperature sensors and current transformers could be use in system, what allows calculation of hot-spot and insulation ageing rate.
Hydrocal 1003-1005 (MTE Meter Test Equipment, Switzerland) - Intelligent system for the individual measurement of dissolvedgas in oil contents:
and moisture (H2O) in the insulating oil of power transformers. Hydrocal is mounted on a valve on the transformer tank,without necessity of transformer switch-off.
Graphical firmware Hydrosoft enables Hydrocal parameters setting and data reading from memory. Hydrocal is equipped with communication interfaces for connection with external systems.
Software associated with Hydrocal 1003/1005 system allows:
Parameter | Hydrocal 1003 | Hydrocal 1005 |
|---|---|---|
Measured concentrations | ||
Hydrogen H2 | 0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm | 0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm |
Carbon monoxide CO | 0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm | 0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm |
Moinsture-in-oil H2O | absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm | absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm |
Acethylene C2H2 | 0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 5 ppm | |
Ethylene C2H4 | 0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 10 ppm | |
Operation temperature | Oil Temperature: -20 °C ... +90 °C Ambient temperature: -50 °C ... +55 °C | Oil Temperature: -20 °C ... +90 °C Ambient temperature: -50 °C ... +55 °C |
Analogue outputs (4…20 mA) | 3 x analogue outputs: 4-20 mA (H2, CO, H2O concentration) 1 x analogue outputs: 4 ... 20 mA (free configurable) | 5 x analogue outputs (H2, C2H2, C2H4, CO, H2O, configurable) |
Digital outputs | 4 x 12 V relay outputs (20 V DC / V AC, 2A, 60 W) 8 x opto-coupler outputs | 5 x 12 V DC-relay outputs 5 x 5 V DC opto-coupler outputs |
Analogue inputs | 4 x analogue DC inputs: 0/4 ... 20 mA 4 x analogue inputs: 0/4 ... 20 mA / 0 ... 10 V (configurable by jumpers) | 4 x analogue DC inputs: 0/4 ... 20 mA 6 x analogue AC inputs: 0 ... 80 V +20% |
Communication | RS-232, RS-485, internal on-board modem (GSM 14.4 kBit / analogue 56 kBit) | RS-232, RS-485, Ethernet (copper-wired or fibre optical) |
Protection class | IP 55 | IP 55 |
Power supply | 110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz | 110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz |
Dimensions | 215 x 215 x 215 mm | 263 x 263 x 257 mm |
Weight | approx. 8 kg | approx. 9 kg |