Select your language

Hydrocal 1003/1005 System

System Hydrocal 1003

PURPOSE

Monitoring system SMT-EE is designed for transformer on-line diagnostics. It consists of Hydrocal device for gas-in-oil and moisturein-oil measurements, ZVCM 1001 device for bushings monitoringand SMT software for data visualization and processing. Additional signals from temperature sensors and current transformers could be use in system, what allows calculation of hot-spot and insulation ageing rate.

DESCRIPTION

Hydrocal 1003-1005 (MTE Meter Test Equipment, Switzerland) - Intelligent system for the individual measurement of dissolvedgas in oil contents:

  • hydrogen (H2) and carbon monoxide CO – model 1003
  • hydrogen (H2), carbon monoxide CO, acetylene (C2H2),ethylene (C2H4) – model 1005

and moisture (H2O) in the insulating oil of power transformers. Hydrocal is mounted on a valve on the transformer tank,without necessity of transformer switch-off.

 

Graphical firmware Hydrosoft enables Hydrocal parameters setting and data reading from memory. Hydrocal is equipped with communication interfaces for connection with external systems.

 

Software associated with Hydrocal 1003/1005 system allows:

  • on-line, remote monitoring of all measured values,
  • trends of gas-in-oil and moisture content,
  • notifying user in case of alarm (by SMS too),
  • communication with external SCADA systems.

TECHNICAL DATA

Parameter

Hydrocal 1003

Hydrocal 1005

Measured concentrations

Hydrogen H2

0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm

0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm

Carbon monoxide CO

0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm

0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm

Moinsture-in-oil H2O

absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm

absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm

Acethylene C2H2

0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 5 ppm

Ethylene C2H4

0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 10 ppm

Operation temperature

Oil Temperature: -20 °C ... +90 °C

Ambient temperature: -50 °C ... +55 °C

Oil Temperature: -20 °C ... +90 °C

Ambient temperature: -50 °C ... +55 °C

Analogue outputs (4…20 mA)

3 x analogue outputs: 4-20 mA (H2, CO, H2O concentration)

1 x analogue outputs: 4 ... 20 mA (free configurable)

5 x analogue outputs (H2, C2H2, C2H4, CO, H2O, configurable)

Digital outputs

4 x 12 V relay outputs (20 V DC / V AC, 2A, 60 W)

8 x opto-coupler outputs

5 x 12 V DC-relay outputs

5 x 5 V DC opto-coupler outputs

Analogue inputs

4 x analogue DC inputs: 0/4 ... 20 mA

4 x analogue inputs: 0/4 ... 20 mA / 0 ... 10 V (configurable by jumpers)

4 x analogue DC inputs: 0/4 ... 20 mA

6 x analogue AC inputs: 0 ... 80 V +20%

Communication

RS-232, RS-485, internal on-board modem (GSM 14.4 kBit / analogue 56 kBit)

RS-232, RS-485, Ethernet (copper-wired or fibre optical)

Protection class

IP 55

IP 55

Power supply

110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz

110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz

Dimensions

215 x 215 x 215 mm

263 x 263 x 257 mm

Weight

approx. 8 kg

approx. 9 kg

All questions should be directed to:

mgr inż. Jerzy Buchacz

This email address is being protected from spambots. You need JavaScript enabled to view it.
tel: 32 237 66 30

Image

We Provide The Power of Renewable Energy.

We successfully cope with tasks of varying complexity, provide long-term guarantees and regularly master new technologies.

Got a project in mind?